Laserfiche WebLink
Chapter 69 <br /> (3) N.E.C. 230.70 (a) Location. The service disconnecting means shall be installed at a <br /> readily accessible location either outside of a building or structure, or inside nearest point of <br /> entrance of the service conductors, but not to exceed ten feet. <br /> (Amended, Ordinance No. 2005-81, September 6, 2005) <br /> (4) Where city water is available, the electrical service shall be bonded to the cold water <br /> piping with a jumper around the water meter. <br /> (Amended, Ordinance No. 2005-81, September 6, 2005) <br /> (Amended, Ordinance No. 2002-16,April 1, 2002) <br /> (Amended, Ordinance No. 2000-96,November 6, 2000) <br /> 5 Sizing of service entrance conductors shall be one of the following: a to main <br /> ( ) g g ( ) <br /> breaker with no reduction of ampere rating; (b) to approved calculated load where multiple <br /> disconnects are used, with no reduction of ampere rating; (c) to rated buss of equipment when no <br /> calculated load is provided with no reduction of ampere rating. <br /> (Amended, Ordinance No. 2008-09,March 17, 2008) <br /> (Amended, Ordinance No. 2005-81, September 6, 2005) <br /> (Amended, Ordinance No. 2002-42,May 20, 2002) <br /> (6) PVC risers up utility poles shall be Schedule 80. <br /> (Amended, Ordinance No. 2008-09, March 17, 2008) <br /> (7) Metal elbows and conduits at utility poles and building service shall be connected to <br /> an effective grounding path, by the electrical contractor and installed as per N.E.C. 250.80. <br /> (Amended, Ordinance No. 2008-09, March 17, 2008) <br /> 10. CODE APPLICATIONS - SPECIFIC. <br /> A. New buildings of all types: <br /> 1) The 2011 edition of the National Fire Protection Association will be the accepted <br /> code for all electrical wiring installations. <br /> (Amended, Ordinance No. 2008-09, March 17, 2008) <br />