Laserfiche WebLink
, � <br /> , ; . <br /> 9. UTILITY SPECIFICATIONS. <br /> a. All newly installed electrical services shall be in <br /> conformance with "Electrical Meter Standards for Electrical <br /> Contractors," effective January 1, 1991, by Illinois Power, un- <br /> less otherwise provided herein. <br /> b. Where city water supply is available, the electri- <br /> cal service shall be grounded to the cold water pipinq with a <br /> jumper around the water meter. <br /> 10. CODE APPLICATIONS - SPECIFIC. <br /> A. New buildinqs of all types: <br /> (1) The 1990 edition of the National Fire Protec- <br /> tion Association will be the accepted code <br /> for all electrical wirinq installations with <br /> the exception of Article 230-70 (a) "Location <br /> of service disconnectinq means. " Said Ar- <br /> ticle 230-70 is here by amended to provide as I <br /> follows: � <br /> "The service disconnecting means shall be in- <br /> stalled at a readily accessible location <br /> either outside of a building or structure, or <br /> inside nearest the point of entrance of the <br /> service conductors, but not to exceed ten <br /> feet." <br /> B. Existing buildings: <br /> (1) Other than dwellinq: <br />