Laserfiche WebLink
s39-'�L 907.4.2 substitute"...fire alarm system is required"for"...fire alarm system is <br /> installed". <br /> �1!1G 7 l. �;+„�o« G(1,. +» � cc � +» <br /> £-��z�vT�2�EFP13�9i3�ao�crccrcc�vpci-ccirc--r9�—r�perccn� <br /> D„L,1;.. A„��}Flln� !1'7�1 <br /> , cc <br /> » <br /> Section 8. New and existing buildings shall have approved address numbers, building <br /> numbers or approved building identification placed in a position that is plainly legible and visible <br /> from the street or road fronting the property. These numbers shall contrast with their <br /> background. Address numbers shall be Arabic numerals or Alphabet letters. Numbers <br /> shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 <br /> mm). The code enforcement official may require additional numbers as needed. (Reference: <br /> �A99 2015 International Fire Code Section 505.1 Premises Identification). <br /> Section 912.2.1 of the �A99 2015 International Fire Code shall be amended, so that as <br /> so amended, the Fire Department Connection Visible Location, will provide as follows: The <br /> location of any Fire Department connection shall be indicated with a strobe located <br /> approxirriately ten feet above grade and within ten feet of the vertical aacis of the Fire Department <br /> Connection. <br /> ARTICLE II.BASIC FIIZE CONTROL MEASURES AND REGULATIONS <br /> 20.EMERGENCY LIGHTS: Emergency lights shall be required for all new <br /> construction of public buildings as well as permit required renovations in all common use restrooms, <br />