Laserfiche WebLink
ar�A ' ._- _ �.:� <br /> - «.i _�'l.:° �`�6. <br /> _'F._'� <br /> _=J= <br /> ELECTRICAL INSTALLATION NOTES � � <br /> 23. METAL RECEPTACLE,SWITCH,AND DEVICE BOXES SHALL BE GALVANIZED,EPDXY-COATED;OR <br /> 1. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS NON-CORRODING;SHALL MEET OR EXCEED UL 514A AND NEMA OS 1;AND RATED NEMA 1(OR <br /> THE NATIONAL ELECTRICAL CODE(N.E.C.),AND ALL APPLICABLE LOCAL CODES. BETTER)INDOORS,OR WEATHER PROTECTED(WP OR BETTER)OUTDOORS. � � <br /> N <br /> 2. WIRING RACEWAY AND SUPPORT METHODS AND MATERIALS SHALL COMPLY WITH THE REQUIREMENTS 24. NONMETALLIC RECEPTACLE,SWITCH,AND DEVICE BOXES SHALL MEET OR EXCEED NEMA OS 2; w <br /> OF THE N.E.C. AND RATED NEMA 1(OR BETTER)INDOORS,OR WEATHER PROTECTED(WP OR BETTER)OUTDOORS. � <br /> � <br /> 3. ALL CIRCUITS SHALL BE SEGREGATED AND MAINTAIN MINIMUM CABLE SEPARATION AS REQUIRED BY THE 25. THE SUBCONTRACTOR SHALL NOTIFY AND OBTAIN NECESSARY AUTHORIZATION FROM THE � Q <br /> N.E.C. CONTRACTOR BEFORE COMMENCING WORK ON THE AC POWER DISTRIBUTION PANELS. � <br /> F- <br /> 4. CABLES SHALL NOT BE ROUTED THROUGH LADDER CABLE TRAY RUNGS. 26. THE SUBCONTRACTOR SHALL PROVIDE NECESSARY TAGGING ON THE BREAKERS,CABLES AND W <br /> DISTRIBUTION PANELS IN ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS TO V <br /> 5. EACH END OF EVERY POWER PHASE CONDUCTOR(I.E.,HOTS),GROUNDING,AND T1 CONDUCTOR AND SAFEGUARD AGAINST LIFE AND PROPERTY <br /> CABLE SHALL BE LABELED WITH COLOR-CODED INSULATION OR ELECTRICAL TAPE(3M BRAND,1/2 INCH o <br /> PLASTIC ELECTRICAL TAPE WITH UV PROTECTION,OR EQUAL).THE IDENTIFICATION METHOD SHALL r <br /> CONFORM WITH N.E.C.&OSHA GROUNDING NOTES �r m <br /> 6. ALL ELECTRICAL COMPONENTS SHALL BE CLEARLY LABELED WITH PLASTIC TAPE PER COLOR SCHEDULE, �_�o� <br /> ALL EQUIPMENT SHALL BE LABELED WITH THEIR VOLTAGE RATING,PHASE CONFIGURATION,WIRE 1. ALL GROUND ELECTRODE SYSTEMS(INCLUDING TELECOMMUNICATION,RADIO,LIGHTNING PROTECTION, � <br /> CONFIGURATION,POWER OR AMPACITY RATING,AND BRANCH CIRCUIT ID NUMBERS(I.E.PANEL BOARD AND AC POWER GES'S)SHALL BE BONDED TOGETHER BELOW GRADE,BY TWO OR MORE COPPER �Z=W��, <br /> AND CIRCUIT ID'S). B O N D I N G C O N D U C T O R S I N A C C O R D A N C E W I T H T H E N.E.C. J�o��q <br /> �yG-'A <br /> 7. PANEL BOARDS(ID NUMBERS)AND INTERNAL CIRCUIT BREAKERS(CIRCUIT ID NUMBERS)SHALL BE 2. THE SUBCONTRACTOR SHALL PERFORM IEEE FALL-OF-POTENTIAL RESISTANCE TO EARTH TESTING(PER z m�a�°.g. <br /> CLEARLY LABELED WITH PLASTIC LABELS. I E E E 1 1 0 0 A N D 8 1)F O R G R O U N D E L E C T R O D E S Y S T E M S.T H E S U B C O N T R A C T O R S H A L L F U R N I S H A N D �U S�a� <br /> INSTALL SUPPLEMENTAL GROUND ELECTRODES AS NEEDED TO ACHIEVE A TEST RESULT OF 5 OHMS OR <br /> 8. ALL TIE WRAPS SHALL BE CUT FLUSH WITH APPROVED CUTTING TOOL TO REMOVE SHARP EDGES. LESS. ��,�� <br /> �Olfi <br /> 9. POWER,CONTROL,AND EQUIPMENT GROUND WIRING IN TUBING OR CONDUIT SHALL BE SINGLE 3. THE SUBCONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING GROUNDING AND UNDERGROUND ���„� <br /> CONDUCTOR(#14 AWG OR LARGER),600 V,OIL RESISTANT THHN OR THWN-2,CLASS B STRANDED CONDUIT INSTALLATION AS TO PREVENT ANY LOSS OF CONTINUITY IN THE GROUNDING SYSTEM OR <br /> COPPER CABLE RATED FOR 90°C(WET AND DRI�OPERATION; DAMAGE TO THE CONDUIT&PROVIDE TESTING RESULTS. <br /> LISTED OR LABELED FOR THE LOCATION AND RACEWAY SYSTEM USED,UNLESS OTHERWISE SPECIFIED. 4. METAL CONDUIT AND TRAY SHALL BE GROUNDED AND MADE ELECTRICALLY CONTINUOUS WITH LISTED � a � <br /> 10. SUPPLEMENTAL EQUIPMENT GROUND WIRING LOCATED INDOORS SHALL BE SINGLE CONDUCTOR(#6 BONDING FITTINGS OR BY BONDING ACROSS THE DISCONTINUITY WITH#6 AWG COPPER WIRE UL m a � � m � m <br /> APPROVED GROUNDING TYPE CONDUIT CLAMPS. <br /> AWG OR LARGER),600 V,OIL RESISTANT THHN OR THWN-2 GREEN INSULATION,CLASS B STRANDED � � � � � „ <br /> COPPER CABLE RATED FOR 90°C(VNET AND DR17 OPERATION;LISTED OR LABELED FOR THE LOCATION 5. METAL RACEWAY SHALL NOT BE USED AS THE N.E.C.REQUIRED EQUIPMENT GROUND CONDUCTOR. o � o o � � � <br /> AND RACEWAY SYSTEM USED,UNLESS OTHERWISE NOTED. STRANDED COPPER CONDUCTORS WITH GREEN INSULATION,SIZED IN ACCORDANCE WITH THE N.E.C., o ^ � o <br /> 11. POWER AND CONTROL WIRING,NOT IN TUBING OR CONDUIT,SHALL BE MULTI-CONDUCTOR,TYPE TC SHALL BE FURNISHED AND INSTALLED WITH THE POWER CIRCUITS TO BTS EQUIPMENT. <br /> CABLE(#14 AWG OR LARGER)600 V,OIL RESISTANT THHN OR THHN-2,CLASS B STRANDED COPPER o <br /> 6. CONNECTIONS TO THE GROUND BUS SHALL NOT BE DOUBLED UP OR STACKED.BACK TO BACK F 5 <br /> CABLE RATED FOR 90'C(WET AND DRI�OPERATION;WITH OUTER JACKET;LISTEO OR LABELED FOR Q o <br /> LOCATION USED,UNLESS OTHERWISE SPECIFIED. CONNECTIONS ON OPPOSITE SIDES OF THE GROUND BUS ARE PERMITTED. � w � i o g <br /> z <br /> > <br /> 12. ALL POWER AND GROUNDING CONNECTIONS SHALL BE CRIMP-STYLE,COMPRESSION WIRE LUGS AND 7. ALL EXTERIOR GROUND CONDUCTORS BETWEEN EQUIPMENT/GROUND BARS AND THE GROUND RING y a � � W � o � <br /> WIRENUTS BY THOMAS AND BETTS(OR EQUAL).LUGS AND WIRENUTS SHALL BE RATED FOR OPERATION SHALL BE#2 AWG SOLID TINNED COPPER UNLESS OTHERWISE INDICATED. w � ° w rc a z � <br /> AT NO LESS THAN 75°C(90°C IF AVAILABLE) � o W LL a W o � <br /> 8. ALUMINUM CONDUCTOR OR COPPER CLAD STEEL CONDUCTOR SHALL NOT BE USED FOR GROUNDING � � � � <br /> CONNECTIONS. `�i a a y a �u <br /> 13. RACEWAY AND CABLE TRAY SHALL BE LISTED OR LABELED FOR ELECTRICAL USE IN ACCORDANCE - W � - < <br /> WITH NEMA,UL,ANSI/IEEE,AND N.E.C. ° <br /> 9. USE OF 90°BENDS IN THE PROTECTION GROUNDING CONDUCTORS SHALL BE AVOIDED WHEN 45'BENDS N � <br /> 14. ELECTRICAL METALLIC TUBING(EMT)OR RIGID NONMETALLIC CONDUIT(I.E.,RIGID PVC SCHEDULE CAN BE ADEQUATELY SUPPORTED. <br /> 40,OR RIGID PVC SCHEDULE 80 FOR LOCATIONS SUBJECT TO PHYSICAL DAMAGE)SHALL BE USED 10. EXOTHERMIC WELDS SHALL BE USED FOR ALL GROUNDING CONNECTIONS BELOW GRADE. <br /> FOR EXPOSED INDOOR LOCATIONS. <br /> 15. ELECTRICAL METALLIC TUBING(EMT),ELECTRICAL NONMETALLIC TUBING(EN�,OR RIGID 11. ALL GROUND CONNECTIONS ABOVE GRADE(INTERIOR&EXTERIOR)SHALL BE FORMED USING HIGH Z , ' N � + N <br /> NONMETALLIC CONDUIT(RIGID PVC,SCHEDULE 40)SHALL BE USED FOR CONCEALED INDOOR PRESS CRIMPS. <br /> LOCATIONS. 12. COMPRESSION GROUND CONNECTIONS MAY BE REPLACED BY EXOTHERMIC WELD CONNECTIONS. I L-OO-��54 <br /> 16. GALVANIZED STEEL INTERMEDIATE METALLIC CONDUIT(IMC)SHALL BE USED FOR OUTDOOR �3. ICE BRIDGE BONDING CONDUCTORS SHALL BE EXOTHERMICALLY BONDED OR BOLTED TO THE BRIDGE HWY 36 & 105 <br /> LOCATIONS ABOVE GRADE. <br /> AND THE TOWER GROUND BAR. <br /> 17. RIGID NONMETALLIC CONDUIT(I.E.,RIGID PVC SCHEDULE 40 OR RIGID PVC SCHEDULE 80)SHALL BE 14. APPROVED ANTIOXIDANT COATINGS(I.E.,CONDUCTIVE GEL OR PASTE)SHALL BE USED ON ALL <br /> USED UNDERGROUND;DIRECT BURIED;IN AREAS OF OCCASIONAL LIGHT VEHICLE TRAFFIC OR COMPRESSION AND BOLTED GROUND CONNECTIONS. 2105 E ELDORADO ST <br /> ENCASED IN REINFORCED CONCRETE IN AREAS OF HEAVY VEHICLE TRAFFIC. DECATUR,IL 62521 <br /> 18. LIQUID-TIGHT FLEXIBLE METALLIC CONDUIT(LIQUID-TITE FLEX)SHALL BE USED INDOORS AND 15. ALL EXTERIOR GROUND CONNECTIONS SHALL BE COATED WITH A CORROSION RESISTANT MATERIAL. oRnwN av: e� <br /> OUTDOORS,WHERE VIBRATION OCCURS OR FLEXIBILITY IS NEEDED. <br /> 16. MISCELLANEOUS ELECTRICAL AND NON-ELECTRICAL METAL BOXES,FRAMES AND SUPPORTS SHALL BE CHECKED BY raz <br /> 19. CONDUIT AND TUBING FITTINGS SHALL BE THREADED OR COMPRESSION-NPE AND APPROVED FOR BONDED TOT HE GROUND RING,IN ACCORDANCE WITH THE N.E.C. <br /> DATE 07Y30/15 <br /> THE LOCATION USED.SETSCREWS FITTINGS ARE NOT ACCEPTABLE. 17. BOND ALL METALLIC OBJECTS WITHIN 6 FT.OF MAIN GROUND WIRES WITH 1 #2 AWG TIN-PLATED <br /> � � PROJECT A` 50-170 <br /> 20. CABINETS,BOXES AND WIREWAYS SHALL BE LISTED OR LABELED FOR ELECTRICAL USE IN COPPER GROUND CONDUCTOR. <br /> ACCORDANCE WITH NEMA,UL,ANSI/IEEE,AND N.E.C. sHeerrir�e <br /> 18. GROUND CONDUCTORS USED IN THE FACILITY GROUND AND LIGHTNING PROTECTION SYSTEMS SHALL ELECTRICAL <br /> 21. WIREWAYS SHALL BE EPDXY-COATED(GRAY)AND INCLUDE A HINGED COVER,DESIGNED TO SWING NOT BE ROUTED THROUGH METALLIC OBJECTS THAT FORM A RING AROUND THE CONDUCTOR,SUCH AS AND GROUNDING <br /> OPEN DOWNWARD;SHALL BE PANDUIT TYPE E(OR EQUAL)AND RATED NEMA 1(OR BETTER). METALLIC CONDUITS,METAL SUPPORT CLIPS OR SLEEVES THROUGH WALLS OR FLOORS.WHEN IT IS NOTES <br /> REQUIRED TO BE HOUSED IN CONDUIT TO MEET CODE REQUIREMENTS OR LOCAL CONDITIONS, <br /> 22. EQUIPMENT CABINETS,TERMINAL BOXES,JUNCTION BOXES,AND PULL BOXES SHALL BE NON-METALLIC MATERIAL SUCH AS PVC PLASTIC CONDUIT SHALL BE SUED.WHERE USE OF METAL SHEET NUMBER <br /> GALVANIZED OR EPDXY-COATED SHEET STEEL,SHALL MEET OR EXCEED UL 50,AND RATED NEMA CONDUIT IS UNAVOIDABLE(E.G.,NON-METALLIC CONDUIT PROHIBITED BY LOCAL CODE)THE GROUND <br /> 1(OR BETTER)INDOORS,OR NEMA 3R(OR BETTER)OUTDOORS CONDUCTOR SHALL BE BONDED TO EACH END OF THE METAL CONDUIT. E-� <br />